www.rosemount.comReference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500Hygienic Pressure Transmitter for Life Sciences Applications74
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45002-2CONSIDERATIONSGeneral Measurement accuracy depends upon proper installation of th
Reference Manual 00809-0100-4027, Rev AADecember 20052-3Rosemount 4500Figure 2-2. HART Installation FlowchartSTART HEREBench Calibration?Field Install
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45002-4INSTALLATION PROCEDURESFor dimensional drawing information refer to Appendix A: R
Reference Manual 00809-0100-4027, Rev AADecember 20052-5Rosemount 4500NOTESensor burst pressure limits may be less than clamp pressure limits.NOTEMost
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45002-6HART CommunicatorUsage NoteThe HART Communicator can be used to configure the sec
Reference Manual 00809-0100-4027, Rev AADecember 20052-7Rosemount 4500Connect Wiring and Power UpWiring for HART Protocol NOTEUse shielded twisted pai
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45002-8Grounding Transmitter CaseAlways ground the transmitter case in accordance with
Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comSection 3 ConfigurationCommissioning on the bench With HART . . .
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-2COMMISSIONING ON THE BENCH WITH HARTCommissioning consists of testing the transmi
Reference Manual 00809-0100-4027, Rev AADecember 20053-3Rosemount 4500Wiring Diagrams Bench Hook-upConnect the bench equipment as shown in Figure 3-1
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-4HART COMMUNICATORMenu Tree1. Universal. Rev.2. Field. Dev. Rev.3. Software Rev1.
Reference Manual 00809-0100-4027, Rev AADecember 20053-5Rosemount 4500Fast Key Sequence The following menu indicates fast key sequences for common fun
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-6Review Configuration DataNOTEInformation and procedures in this section that make
Reference Manual 00809-0100-4027, Rev AADecember 20053-7Rosemount 4500CHECK OUTPUT Before performing other transmitter on-line operations, review the
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-8BASIC SETUPSet Process Variable UnitsThe PV Unit command sets the process variabl
Reference Manual 00809-0100-4027, Rev AADecember 20053-9Rosemount 4500Rerange with a HART Communicator OnlyThe easiest way to rerange is to use the HA
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-10Rerange with AMS onlyRight click on the device and select “Configuration Propert
Reference Manual 00809-0100-4027, Rev AADecember 20053-11Rosemount 4500LCD Display ConfigurationThe Meter Options command customizes the LCD display.
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-12Table 3-1. Rosemount (Standard) Alarm and Saturation ValuesTable 3-2. NAMUR-Co
Reference Manual 00809-0100-4027, Rev AADecember 20053-13Rosemount 4500AMSRight click on the device, select “Device Configuration”, then select “Alarm
Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comRosemount 4500 Hygienic Pressure Transmitter . . . .NOTICERead thi
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-14Alarm Level Verification If the transmitter electronics board, Transmitter, or L
Reference Manual 00809-0100-4027, Rev AADecember 20053-15Rosemount 4500Scaled Variable ConfigurationThe scaled variable configuration allows the user
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-16HART CommunicatorTo configure the scaled variable with a HART Communicator, perf
Reference Manual 00809-0100-4027, Rev AADecember 20053-17Rosemount 4500AMS Right click on the device and select “Device Configuration” then select “SV
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-18AMS Right click on the device and select “Device Configuration,” then “Re-mappin
Reference Manual 00809-0100-4027, Rev AADecember 20053-19Rosemount 4500Loop Test The Loop Test command verifies the output of the transmitter, the int
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-20AMSRight click on the device and select “Diagnostics and Test,” then “Loop test”
Reference Manual 00809-0100-4027, Rev AADecember 20053-21Rosemount 45004. Select the back arrow from the HOME/ONLINE screen. The HART Communicator men
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-22AMS Applying a User ConfigurationAny amount of user configurations can be create
Reference Manual 00809-0100-4027, Rev AADecember 20053-23Rosemount 4500AMSRight click on the device and select “Configuration Properties” from the men
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-24The 4500 is set to address zero (0) at the factory, which allows operation in th
Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comSection 4 Operation and MaintenanceCalibration for HART Protocol
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-2Table 4-1. Recommended Calibration TasksNOTE:The transmitter performs to specifi
Reference Manual 00809-0100-4027, Rev AADecember 20054-3Rosemount 4500Figure 4-1 also identifies the approximate transmitter location for each calibra
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-4Determining Calibration FrequencyCalibration frequency can vary greatly depending
Reference Manual 00809-0100-4027, Rev AADecember 20054-5Rosemount 4500Choosing a Trim ProcedureTo decide which trim procedure to use, you must first d
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-6Zero Trim NOTEThe transmitter must be within three percent of true zero (zero-bas
Reference Manual 00809-0100-4027, Rev AADecember 20054-7Rosemount 4500NOTESelect pressure input values so that low and high values are equal to or out
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-8Recall Factory Trim—Analog OutputThis command resets the transmitter analog outpu
Reference Manual 00809-0100-4027, Rev AADecember 20054-9Rosemount 4500AMSRight click on the device and select “Calibrate,” then “D/A Trim” from the me
Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comTable of ContentsSECTION 1IntroductionUsing This Manual . . . . .
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-10a. If Yes is selected, proceed to Step 10.b. If No is selected, repeat Step 8.10
Reference Manual 00809-0100-4027, Rev AADecember 20054-11Rosemount 4500NONPV LIMITA secondary variable read by the transmitter is outside of the trans
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-12SPAN FAILThe span value, set with the local span adjustment button, exceeds the
Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comSection 5 Troubleshooting OVERVIEW Table 5-1 provides summarized m
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45005-2Table 5-1. Rosemount 4500troubleshooting tableSymptom Corrective ActionsTransmit
Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comAppendix A Reference DataSpecifications . . . . . . . . . . . . .
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-2Range and Sensor LimitsFunctional SpecificationsDynamic Performance250 millisecon
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-3Overpressure LimitsTransmitters withstand the following pressure without damage:
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-4Alarm ConfigurationRosemountHigh Alarm: ≥ 21.75 mALow Alarm: ≤ 3.75 mACustom Leve
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-5DIMENSIONAL DRAWINGSFIGURE 1. Dimensional Drawings for the Rosemount 4500 Hygieni
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500TOC-2Scaled Variable Configuration . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-6FIGURE 2. Dimensional Drawings for the Rosemount 4500 Hygienic Pressure Transmitt
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-7FIGURE 3. Dimensional Drawings for the Rosemount 4500 Hygienic Pressure Transmitt
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-8ORDERING INFORMATION Model Transmitter Type4500 Hygienic Pressure TransmitterCod
Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comAppendix B Product CertificatesApproved Manufacturing Locations .
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500B-2HAZARDOUS LOCATIONS CERTIFICATIONSNorth American CertificationsFactory Mutual (FM
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500B-3N1 ATEX Type n (Pending)Certificate No. Baseefa05ATEX0092XATEX Marking: II 3 G E
Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500B-4
Reference Manual 00809-0100-4027, Rev AA12/5/05Rosemount 4500www.rosemount.comIndexAAddressChanging . . . . . . . . . . . . . 3-24Alarm . . . . . .
Reference Manual00809-0100-4027, Rev AA12/5/05Rosemount 4500Index-2PPower supplyHART protocol . . . . . . . . . . 2-7Power up . . . . . . . . . . . .
Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comSection 1 IntroductionUsing This Manual . . . . . . . . . . . .