Rosemount 4500
AMS
Right click on the device and select “Configuration Properties” from the menu
.
1. In the “HART” tab, use the drop down menu to select “Burst Mode ON or
OFF.” For “Burst option” select the desired properties from the drop down
menu. Burst options are as follows:
•PV
% range/current
Process vars/crnt
Process variables
2. After selecting options click Apply.
3. An “Apply Parameter Modification” screen appears, enter desired
information and click OK.
4. After carefully reading the warning provided, select OK.
MULTIDROP
COMMUNICATION
Multidropping transmitters refers to the connection of several transmitters to a
single communications transmission line. Communication between the host
and the transmitters takes place digitally with the analog output of the
transmitters deactivated. Up to fifteen transmitters can be connected on a
single twisted pair of wires, or over leased phone lines.
Multidrop installation requires consideration of the update rate necessary from
each transmitter, the combination of transmitter models, and the length of the
transmission line. Communication with transmitters can be accomplished with
Bell 202 modems and a host implementing HART protocol. Each transmitter
is identified by a unique address (1–15) and responds to the commands
defined in the HART protocol. HART Communicators and AMS can test,
configure, and format a multidropped transmitter the same way as a
transmitter in a standard point-to-point installation.
Figure 3-3 shows a typical multidrop network. This figure is not intended as an
installation diagram.
NOTE
A transmitter in multidrop mode has the analog output fixed at 4 mA. If a
display is installed to a transmitter in multidrop mode, it will alternate the
display between “current fixed” and the specified meter output(s).
Figure 3-3. Typical Multidrop
Network
Power
Supply
Bell 202
Modem
RS-232-C
4500-05_AA.EPS
Page view 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 69 70

Comments to this Manuals

No comments

LevelOne 590903 Handbücher

Bedienungsanleitungen und Benutzerhandbücher für Kabelschnittstelle / Gender-Adapter LevelOne 590903.
Wir stellen 1 PDF-Handbücher LevelOne 590903 zum kostenlosen herunterladen nach Dokumenttypen zur Verfügung Datenblatt






Weitere Produkte und Handbücher für Kabelschnittstelle / Gender-Adapter LevelOne

Modelle Dokumententyp
592001 Datenblatt   LevelOne ADE-8001, 3 Seiten
HVE-9002 Datenblatt   LevelOne HDSpider HDMI Cat.5 Sender, 2 Seiten
ADE-8001 Datenblatt   LevelOne Short Range DVI-D Receiver, 1 Seiten